G15
AUTO/MANUAL SWITCH - 3
INPUTS NAME SYMBOL DATAPOINT
CONTROL OUTPUT CO3 C231
AUTO ENABLE AE3 L186
OUTPUT TRACK VALVE OTV3 C237
OUTPUT TRACK SWITCH SWOTV3 L189
PARAMETERS OUTPUT TRACK ENABLE OTE3 L191
HARD MANUAL LIMIT HML3 L194
OUTPUT HIGH LIMIT OH3 C217
OUTPUT LOW LIMIT OL3 C218
OUTPUT SLEW RATE T33 C226
OUTPUTS
OUTPUT OUT3 C210
OUTPUT TRACK STATUS OVTS3 L177
AUTO STATUS AUT3 L179
Description:
The AUTO/MAN Switch selects one of three signals to load into OUT. The signal
selected is either the Output Tracking Value (OTV), the Auto Value (CO) or the
Manual Pushbutton Value. If the Output Tracking Switch (SWOUT) is zero (0) then
OUT = OTV when Output Tracking is enabled (OTE = 1). When the previous
condition is not in effect OUT will equal CO if Auto Enable = 1 and the A/M
pushbutton has set the Auto Switch to 1. When neither previous condition is in effect
the selected signal comes directly from the output increase and decrease pushbut-
tons.
MODULAR CONTROLLER CUSTOMIZATION GUIDE