requiring standard single loop
functionality.
cASc - for control strategies
requiring cascade functional-
ity.
L.LiM - for control strategies
requiring low limiting function-
ality.
h.LiM - for control strategies
requiring high limiting func-
tionality.
in.Ld - for control strategies
requiring indicator/loader
functionality.
Control
Strategy
A 53SL6000 controller mode
of operation specified with a
selected control scheme, pa-
rameters, and path connec-
tions designed to meet the
specific application needs of
a controlled process.
Derivative
Action (td)
Derivative action (td) is used
for quick attainment of stabil-
ity after sudden process dis-
turbances. It augments
proportional action by re-
sponding to the rate of
change of the process vari-
able. Derivative action is en-
tered as the time proportional
action is advanced, from 0.01
minutes (minimum action) to
8 minutes (maximum action);
0 is off.
Digital
Read-Out
(dro)
An LED field used to display
alphanumerics. The
53SL6000 controller has
three dros: red, which is a
four character field used pri-
marily for the process vari-
able value in engineering
units; green, which is a four
character field used primarily
for the setpoint value in engi-
neering units; and yellow,
which is a three character
field used primarily for the
output value expressed as a
percentage of the final control
element excursion or operat-
ing band.
Digital-
to-
Analog
Converter
Mode
An operating mode of the
characterizer whereby values
are entered into chr parame-
ter constants K1 and K2,
which are used as multipliers
for the digital inputs at chr.b
and chr.c respectively. The
product of (chr.b)(K1) is
added to the characterizer
base value (not user ac-
cessable) and the product of
(chr.c)(K2) is subtracted from
the characterizer base value.
It is the interaction of these
two inputs, chr.b and chr.c on
the base that causes the ana-
log output
Discrete
Input (DI)
Discrete inputs 1-4 are input
enables that can also be used
as event indicators to gener-
ate logic levels based on the
applied input voltage. (Dis-
crete inputs 3 and 4 require
the 2DI/2DO option module.)
The remainder of the discrete
inputs 5-8 do not receive in-
puts from external sources.
Discrete
Output (DO)
Discrete outputs 1-4 convert
logic levels to hardware con-
tact conditions. (Discrete
outputs 3 and 4 require the
optional 2DI/2DO module.)
The remainder of the discrete
outputs 5-8 do not provide ex-
ternal outputs from the con-
troller.
Display
Panel
The 53SL6000 controller
functionality for the faceplate
push buttons and LEDs.
Dual
Indicator with
Re-Transmitted
Process
Variable
A control strategy whereby
two analog inputs can be dis-
played and either one can be
selected as the re-transmitted
output. This control strategy
is implemented with the fac-
tory default settings and by
selecting the in.Ld prompt for
ProG-cS-SchM parameter.
Easy-Tune
The 53SL6000 controller
automatic tuning algorithm
that approximates a first or-
der time lag with gain and
dead-time to determine the
53SL6000 Instruction Manual Appendix A. Glossary
A-2