Command Series Migration to MOD 30ML
Pre-configured Dual Loop PID with Remote SP
To configure the inputs:
Open the AIN block AIN1 for input 1. See figure below:
Figure P4.2.
Dual PID with
Remote SP
You can change the Input Type and Linearization Type for the built-in input 1 here.
Specify the Input Signal Range also.
The VCI block ENG UNITS 1 in the loop compound is used for converting the voltage,
millivolts or current input signal to engineering units. See figure below:
Change the Linearization type (Linear, Square, Square root, Modified Square, Modified
Square root) as required for the input signal and specify the Engineering Range and
Quality Limits.
P4- 5