IB-23C650
BASIC OPERATION
Auto/Manual Transfer for On-Off Control
If the controller is set up for on-off control, the bumpless transfer feature does
not apply when switching from automatic to manual. When switched to
manual, the on-off controller output is always initialized at 0%. The transfer is
bumpless only if the automatic output happens to be at 0% when switched.
Operation in manual is the same as for a time proportioning controller. When
switching from manual back to automatic, operation is the same as for all other
types of control.
137