Micromod MOD: Modcell 2050R Users Guide Uživatelský manuál Strana 168

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 228
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 167
IB-23C650
TUNING
Table 13. Autotune Procedure
Step Step Description
Top
Display
7
Process High Trip-Point.
UP
or
DN
adjusts process high trip-point value.
SCRL
to Step 8 or press and hold
SCRL
to return
to
STEP SIZ (Step 5).
TAG NAME
8 Process Low Trip-Point.
UP
or
DN
adjusts process low trip-point value.
SCRL
to Step 9 or press and hold
SCRL
to return
to
STEP SIZ (Step 5).
TAG NAME
9 Parameter Tune Selection.
UP
or
DN
selects PI or PID tuning.
SCRL
to start autotune execution Step 10.
Note: Autotune cycle can be canceled by
pressing the auto key.
TAG NAME
10 Autotune Execution.
If autotune was successful but there is a caution
message, go to Step 11.
If autotune was successful and there is no
message, return to Process/Set-Point display.
If autotune was not successful, go to Step 12.
TAG NAME
11 Autotune Caution.
SCRL
to advance to:
Step 11.1 for an increase step size message, or
Step 11.2 for a response limited message.
TAG NAME
162