Single Loop Process Controller Instruction Manual
Easy-Tune 111
11.6 Aborting the EASY-TUNE Sequence
If the EASY-TUNE sequence is active and the instrument output is deliberately changed, the sequence will
be aborted. The original instrument output and Manual or Auto mode will be restored. Datapoint B387,
EASY-TUNE Status, will be set to 54.
If the EASY-TUNE sequence is active and datapoint L521, EASY-TUNE Abort Switch, is set to 1, the
sequence is immediately aborted. The original instrument output and Manual or Auto mode will be
restored. Datapoint B387, EASY-TUNE Status, will be set to 60.
11.7 EASY-TUNE Sequence Completion
Upon successful completion of the EASY-TUNE sequence, the instrument is returned to its original status,
with or without the new tuning parameters, depending on its initial settings. If the EASY-TUNE algorithm
encounters an abnormal event, the instrument is returned to its original settings and an error status is dis-
played in datapoint B387.