Single Loop Process Controller Instruction Manual
42 Configuration Parameters
4.2 Factory Standard Configuration
The instrument is shipped from the factory configured as summarized in Table 4-2.
If the state of the database is unknown, the instrument can be returned to the factory standard
configuration with two datapoint entries:
1. Set B00 to 98 to default the database.
2. Set B00 to 1 to start functioning as a Single Loop Controller.
If the unit is to be operated online, it must be installed as described in Section 2, Installation.
ANI0 (PV Input) and ANO0 (Output) must be connected, and the unit must have power applied.
Table 4-2. Factory Standard Configuration
Datapoint Value Attribute
B000 1
This value indicates Single Loop PID Controller operation.
C106 100
Proportional Band = 100%.
C107 0
No Reset (TR) action.
C108 0
No Derivative (TD) action.
B335 1
No Alarms.
C256 100
ANI0 Engineering Span Input (Process Variable [PV] Input) = 0% - 100%.
L416 0
ANI0 Input Voltage Range is 1 - 5 V.
L106 1
Reverse Switch is set so that the instrument output decreases as PV increases.
L115 0
Remote Setpoint Disabled indicates the setpoint value established in Local
mode remains in effect when the instrument is placed in Remote mode.
Displays
1. As configured: Display of Single Loop Controller, Analog Back-up Controller,
Ratio Controller, or Automatic Manual Station
2. Parameter 1 Display