MOD 30ML Operation
APPENDIX A - EVENT CODES
A-3
Table A-2. Event Codes, Description and Action (Cont’d)
Block
Type
Codes Full Message Text Description/Action
DDOM 4 BLOCK MODE_1 SET TO AUTO Information only.
DDOM 5 BLOCK MODE_1 SET TO MANUAL Information only.
DDOM 6 BLOCK MODE_2 SET TO AUTO Information only.
DDOM 7 BLOCK MODE_2 SET TO MANUAL Information only.
DDOM 8 I/O MISMATCH A slot configured for a digital module contains
an intelligent module (analog input, analog
output, ICN, MSC or RIO).
NOTE: This diagnostic cannot distinguish
between an empty slot and a digital I/O module
or between different types of digital modules.
DDOM 9 DDO_1_MODULE_ERROR The select circuit, which is used to
communicate with the module blocks, has a
diagnostic error. In this case, all modules
report this diagnostic.
DDOM 10 DDO_2_MODULE_ERROR Same as Code 9.
DI 0 BLOCK STATE SET TO RUN Information only.
DI 1 BLOCK STATE SET TO HOLD Information only.
DI 2 BLOCK STATE SET TO OFF Information only.
DI 3 BLOCK STATE SET TO DEBUG Information only.
DIF 4 FACEPLATE COMMUNICATIONS ERROR An error occurred when trying to communicate
with the faceplate. Instances are counted in
CMERRCTR or BFULLCTR.
DIF 5 NO KEYBOARD RESPONSE The faceplate failed to respond when keyboard
data was requested. Instances are counted in
KBERRCTR.
DIM 4 BLOCK MODE SET TO AUTO Information only.
DIM 5 BLOCK MODE SET TO MANUAL Information only.
DIM 6 I/O MISMATCH A slot configured for a digital module contains
an intelligent module (analog input, analog
output, ICN, MSC or RIO).
NOTE: This diagnostic cannot distinguish
between an empty slot and a digital I/O module
or between different types of digital modules.
DISP 4 INVALID DISPLAY OPERATION
ATTEMPTED (Ack Only Diag).
This error is reported if for example, an attempt
is made (via key event statement or remote
source) to perform some illegal operation.
DOM 4 BLOCK MODE SET TO AUTO Information only.
DOM 5 BLOCK MODE SET TO MANUAL Information only.
DOM 6 I/O MISMATCH A slot configured for a digital module contains
an intelligent module (analog input, analog
output, ICN, MSC or RIO).
NOTE: This diagnostic cannot distinguish
between an empty slot and a digital I/O module
or between different types of digital modules.
DOM 7 DO_MODULE_ERROR The select circuit, which is used to
communicate with the module blocks, has a
diagnostic error. In this case, all modules
report this diagnostic.
Komentáře k této Příručce