MOD 30ML Operation
APPENDIX A - EVENT CODES
A-13
Table A-2. Event Codes, Description and Action
Block
Type
Codes Full Message Text Description/Action
PID 0 BLOCK STATE SET TO RUN Information only.
PID 1 BLOCK STATE SET TO HOLD Information only.
PID 2 BLOCK STATE SET TO OFF Information only.
PID 3 BLOCK STATE SET TO DEBUG Information only.
PID 4 CALCULATION ERROR A calculation error (calculation overflow, divide
by zero, etc.) has been detected in calculations
which do not affect the control output (e.g.,
adjusted set-point calculation). The block
completes the calculation using some
reasonable value (+ or - maximum value for
overflows, etc.), and sets the output qualities
according to the configuration of Attribute No.
58, Calculation Error Action (CERRACT). The
diagnostic error clears and the quality is set
back to good when a subsequent execution of
the block performs a successful calculation.
PID 5 CONTROL OUTPUT CALCULATION
ERROR
A calculation error (calculation overflow, divide
by zero, etc.) has been detected while
calculating the control output value. The block
completes the calculation using some
reasonable value (+ or - maximum value for
overflows, etc.), and sets the output qualities
according to the configuration of Attribute No.
58, Calculation Error Action (CERRACT).. The
diagnostic error clears and the quality is set
back to good when a subsequent execution of
the block performs a successful calculation.
RDIM 4 CHANNEL 0 MODE SET TO AUTO Information only.
RDIM 5 CHANNEL 0 MODE SET TO MANUAL Information only.
RDIM 6 ••• Repeat for Channels 1 to 14
RDIM 34 CHANNEL 15 MODE SET TO AUTO Information only.
RDIM 35 CHANNEL 15 MODE SET TO MANUAL Information only.
RDIM 36 I/O MISMATCH A configured address on the CS-31 bus is not
used or the installed remote module does not
match the address configuration.
RDIM 37 MODULE EXTENDED ERROR A remote module has reported an error.
Codes identifying reported error are stored in
the block database as extended errors. The
error codes can be viewed via Attribute Nos. 31
- 46, Extended Error (EXTERR).