MOD 30ML Operation
APPENDIX A - EVENT CODES
A-17
Table A-2. Event Codes, Description and Action
Block
Type
Codes Full Message Text Description/Action
SEQ 0 BLOCK STATE SET TO RUN Information only.
SEQ 1 BLOCK STATE SET TO HOLD Information only.
SEQ 2 BLOCK STATE SET TO OFF Information only.
SEQ 3 BLOCK STATE SET TO DEBUG Information only.
SEQ 4 SEQ BLOCK BAD INPUT DETECTED Bad quality has been detected in an external
step input or transition expression input. The
block takes action in accordance with the
configuration of Attribute No. 41, Bad Input
Action (IACTION).
SEQ 5 SEQ BLOCK CALC ERROR A calculation error (calculation overflow, divide
by zero, etc.) has been detected in a
calculation to evaluate a transition expression.
The block completes the calculation using
some reasonable value (+ or - maximum value
for overflows and divide by zero), and takes
action in accordance with the configuration of
Attribute No. 42, Calculation Error Action
(CACTION).
SEQ 6 SEQ BLOCK STEP OUT OF RANGE A calculated step is out of range or a syntax
error has been detected in a transition
expression. The block takes action in
accordance with the configuration of Attribute
No. 43, Bad Step Error Action (SACTION).
SEQ 7 SEQ BLOCK FAILURE As a result of a bad input error, calculation error
or step out of range error (Event Code 4, 5 or
6), the sequence has been driven to the Fail
Step
SEQ 8 BLOCK SET TO MANUAL Information only.
SEQ 9 BLOCK MODE SET TO AUTO Information only.
SEQ 10 BLOCK MODE SET TO SEMI-AUTO Information only.